+Internet Engineering Task Force (IETF) J. Martocci, Ed.
+Request for Comments: 5867 Johnson Controls Inc.
+Category: Informational P. De Mil
+ISSN: 2070-1721 Ghent University - IBCN
+ N. Riou
+ Schneider Electric
+ W. Vermeylen
+ Arts Centre Vooruit
+ June 2010
+
+
+ Building Automation Routing Requirements
+ in Low-Power and Lossy Networks
+
+Abstract
+
+ The Routing Over Low-Power and Lossy (ROLL) networks Working Group
+ has been chartered to work on routing solutions for Low-Power and
+ Lossy Networks (LLNs) in various markets: industrial, commercial
+ (building), home, and urban networks. Pursuant to this effort, this
+ document defines the IPv6 routing requirements for building
+ automation.
+
+Status of This Memo
+
+ This document is not an Internet Standards Track specification; it is
+ published for informational purposes.
+
+ This document is a product of the Internet Engineering Task Force
+ (IETF). It represents the consensus of the IETF community. It has
+ received public review and has been approved for publication by the
+ Internet Engineering Steering Group (IESG). Not all documents
+ approved by the IESG are a candidate for any level of Internet
+ Standard; see Section 2 of RFC 5741.
+
+ Information about the current status of this document, any errata,
+ and how to provide feedback on it may be obtained at
+ http://www.rfc-editor.org/info/rfc5867.
+
+
+
+
+
+
+
+
+
+
+
+
+
+Martocci, et al. Informational [Page 1]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+Copyright Notice
+
+ Copyright (c) 2010 IETF Trust and the persons identified as the
+ document authors. All rights reserved.
+
+ This document is subject to BCP 78 and the IETF Trust's Legal
+ Provisions Relating to IETF Documents
+ (http://trustee.ietf.org/license-info) in effect on the date of
+ publication of this document. Please review these documents
+ carefully, as they describe your rights and restrictions with respect
+ to this document. Code Components extracted from this document must
+ include Simplified BSD License text as described in Section 4.e of
+ the Trust Legal Provisions and are provided without warranty as
+ described in the Simplified BSD License.
+
+ This document may contain material from IETF Documents or IETF
+ Contributions published or made publicly available before November
+ 10, 2008. The person(s) controlling the copyright in some of this
+ material may not have granted the IETF Trust the right to allow
+ modifications of such material outside the IETF Standards Process.
+ Without obtaining an adequate license from the person(s) controlling
+ the copyright in such materials, this document may not be modified
+ outside the IETF Standards Process, and derivative works of it may
+ not be created outside the IETF Standards Process, except to format
+ it for publication as an RFC or to translate it into languages other
+ than English.
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+Martocci, et al. Informational [Page 2]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+Table of Contents
+
+ 1. Introduction ....................................................4
+ 2. Terminology .....................................................6
+ 2.1. Requirements Language ......................................6
+ 3. Overview of Building Automation Networks ........................6
+ 3.1. Introduction ...............................................6
+ 3.2. Building Systems Equipment .................................7
+ 3.2.1. Sensors/Actuators ...................................7
+ 3.2.2. Area Controllers ....................................7
+ 3.2.3. Zone Controllers ....................................8
+ 3.3. Equipment Installation Methods .............................8
+ 3.4. Device Density .............................................9
+ 3.4.1. HVAC Device Density .................................9
+ 3.4.2. Fire Device Density .................................9
+ 3.4.3. Lighting Device Density ............................10
+ 3.4.4. Physical Security Device Density ...................10
+ 4. Traffic Pattern ................................................10
+ 5. Building Automation Routing Requirements .......................12
+ 5.1. Device and Network Commissioning ..........................12
+ 5.1.1. Zero-Configuration Installation ....................12
+ 5.1.2. Local Testing ......................................12
+ 5.1.3. Device Replacement .................................13
+ 5.2. Scalability ...............................................13
+ 5.2.1. Network Domain .....................................13
+ 5.2.2. Peer-to-Peer Communication .........................13
+ 5.3. Mobility ..................................................13
+ 5.3.1. Mobile Device Requirements .........................14
+ 5.4. Resource Constrained Devices ..............................15
+ 5.4.1. Limited Memory Footprint on Host Devices ...........15
+ 5.4.2. Limited Processing Power for Routers ...............15
+ 5.4.3. Sleeping Devices ...................................15
+ 5.5. Addressing ................................................16
+ 5.6. Manageability .............................................16
+ 5.6.1. Diagnostics ........................................17
+ 5.6.2. Route Tracking .....................................17
+ 5.7. Route Selection ...........................................17
+ 5.7.1. Route Cost .........................................17
+ 5.7.2. Route Adaptation ...................................18
+ 5.7.3. Route Redundancy ...................................18
+ 5.7.4. Route Discovery Time ...............................18
+ 5.7.5. Route Preference ...................................18
+ 5.7.6. Real-Time Performance Measures .....................18
+ 5.7.7. Prioritized Routing ................................18
+
+
+
+
+
+
+
+Martocci, et al. Informational [Page 3]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+ 5.8. Security Requirements .....................................19
+ 5.8.1. Building Security Use Case .........................19
+ 5.8.2. Authentication .....................................20
+ 5.8.3. Encryption .........................................20
+ 5.8.4. Disparate Security Policies ........................21
+ 5.8.5. Routing Security Policies to Sleeping Devices ......21
+ 6. Security Considerations ........................................21
+ 7. Acknowledgments ................................................22
+ 8. References .....................................................22
+ 8.1. Normative References ......................................22
+ 8.2. Informative References ....................................22
+ Appendix A. Additional Building Requirements ......................23
+ A.1. Additional Commercial Product Requirements ................23
+ A.1.1. Wired and Wireless Implementations .................23
+ A.1.2. World-Wide Applicability ...........................23
+ A.2. Additional Installation and Commissioning Requirements ....23
+ A.2.1. Unavailability of an IP Network ....................23
+ A.3. Additional Network Requirements ...........................23
+ A.3.1. TCP/UDP ............................................23
+ A.3.2. Interference Mitigation ............................23
+ A.3.3. Packet Reliability .................................24
+ A.3.4. Merging Commissioned Islands .......................24
+ A.3.5. Adjustable Routing Table Sizes .....................24
+ A.3.6. Automatic Gain Control .............................24
+ A.3.7. Device and Network Integrity .......................24
+ A.4. Additional Performance Requirements .......................24
+ A.4.1. Data Rate Performance ..............................24
+ A.4.2. Firmware Upgrades ..................................25
+ A.4.3. Route Persistence ..................................25
+
+1. Introduction
+
+ The Routing Over Low-Power and Lossy (ROLL) networks Working Group
+ has been chartered to work on routing solutions for Low-Power and
+ Lossy Networks (LLNs) in various markets: industrial, commercial
+ (building), home, and urban networks. Pursuant to this effort, this
+ document defines the IPv6 routing requirements for building
+ automation.
+
+ Commercial buildings have been fitted with pneumatic, and
+ subsequently electronic, communication routes connecting sensors to
+ their controllers for over one hundred years. Recent economic and
+ technical advances in wireless communication allow facilities to
+ increasingly utilize a wireless solution in lieu of a wired solution,
+ thereby reducing installation costs while maintaining highly reliant
+ communication.
+
+
+
+
+
+Martocci, et al. Informational [Page 4]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+ The cost benefits and ease of installation of wireless sensors allow
+ customers to further instrument their facilities with additional
+ sensors, providing tighter control while yielding increased energy
+ savings.
+
+ Wireless solutions will be adapted from their existing wired
+ counterparts in many of the building applications including, but not
+ limited to, heating, ventilation, and air conditioning (HVAC);
+ lighting; physical security; fire; and elevator/lift systems. These
+ devices will be developed to reduce installation costs while
+ increasing installation and retrofit flexibility, as well as
+ increasing the sensing fidelity to improve efficiency and building
+ service quality.
+
+ Sensing devices may be battery-less, battery-powered, or mains-
+ powered. Actuators and area controllers will be mains-powered. Due
+ to building code and/or device density (e.g., equipment room), it is
+ envisioned that a mix of wired and wireless sensors and actuators
+ will be deployed within a building.
+
+ Building management systems (BMSs) are deployed in a large set of
+ vertical markets including universities, hospitals, government
+ facilities, kindergarten through high school (K-12), pharmaceutical
+ manufacturing facilities, and single-tenant or multi-tenant office
+ buildings. These buildings range in size from 100K-sq.-ft.
+ structures (5-story office buildings), to 1M-sq.-ft. skyscrapers
+ (100-story skyscrapers), to complex government facilities such as the
+ Pentagon. The described topology is meant to be the model to be used
+ in all of these types of environments but clearly must be tailored to
+ the building class, building tenant, and vertical market being
+ served.
+
+ Section 3 describes the necessary background to understand the
+ context of building automation including the sensor, actuator, area
+ controller, and zone controller layers of the topology; typical
+ device density; and installation practices.
+
+ Section 4 defines the traffic flow of the aforementioned sensors,
+ actuators, and controllers in commercial buildings.
+
+ Section 5 defines the full set of IPv6 routing requirements for
+ commercial buildings.
+
+
+
+
+
+
+
+
+
+Martocci, et al. Informational [Page 5]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+ Appendix A documents important commercial building requirements that
+ are out of scope for routing yet will be essential to the final
+ acceptance of the protocols used within the building.
+
+ Section 3 and Appendix A are mainly included for educational
+ purposes.
+
+ The expressed aim of this document is to provide the set of IPv6
+ routing requirements for LLNs in buildings, as described in
+ Section 5.
+
+2. Terminology
+
+ For a description of the terminology used in this specification,
+ please see [ROLL-TERM].
+
+2.1. Requirements Language
+
+ The key words "MUST", "MUST NOT", "REQUIRED", "SHALL", "SHALL NOT",
+ "SHOULD", "SHOULD NOT", "RECOMMENDED", "MAY", and "OPTIONAL" in this
+ document are to be interpreted as described in [RFC2119].
+
+3. Overview of Building Automation Networks
+
+3.1. Introduction
+
+ To understand the network systems requirements of a building
+ management system in a commercial building, this document uses a
+ framework to describe the basic functions and composition of the
+ system. A BMS is a hierarchical system of sensors, actuators,
+ controllers, and user interface devices that interoperate to provide
+ a safe and comfortable environment while constraining energy costs.
+
+ A BMS is divided functionally across different but interrelated
+ building subsystems such as heating, ventilation, and air
+ conditioning (HVAC); fire; security; lighting; shutters; and
+ elevator/lift control systems, as denoted in Figure 1.
+
+ Much of the makeup of a BMS is optional and installed at the behest
+ of the customer. Sensors and actuators have no standalone
+ functionality. All other devices support partial or complete
+ standalone functionality. These devices can optionally be tethered
+ to form a more cohesive system. The customer requirements dictate
+ the level of integration within the facility. This architecture
+ provides excellent fault tolerance since each node is designed to
+ operate in an independent mode if the higher layers are unavailable.
+
+
+
+
+
+Martocci, et al. Informational [Page 6]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+ +------+ +-----+ +------+ +------+ +------+ +------+
+
+ Bldg App'ns | | | | | | | | | | | |
+
+ | | | | | | | | | | | |
+
+ Building Cntl | | | | | S | | L | | S | | E |
+
+ | | | | | E | | I | | H | | L |
+
+ Area Control | H | | F | | C | | G | | U | | E |
+
+ | V | | I | | U | | H | | T | | V |
+
+ Zone Control | A | | R | | R | | T | | T | | A |
+
+ | C | | E | | I | | I | | E | | T |
+
+ Actuators | | | | | T | | N | | R | | O |
+
+ | | | | | Y | | G | | S | | R |
+
+ Sensors | | | | | | | | | | | |
+
+ +------+ +-----+ +------+ +------+ +------+ +------+
+
+ Figure 1: Building Systems and Devices
+
+3.2. Building Systems Equipment
+
+3.2.1. Sensors/Actuators
+
+ As Figure 1 indicates, a BMS may be composed of many functional
+ stacks or silos that are interoperably woven together via building
+ applications. Each silo has an array of sensors that monitor the
+ environment and actuators that modify the environment, as determined
+ by the upper layers of the BMS topology. The sensors typically are
+ at the edge of the network structure, providing environmental data
+ for the system. The actuators are the sensors' counterparts,
+ modifying the characteristics of the system, based on the sensor data
+ and the applications deployed.
+
+3.2.2. Area Controllers
+
+ An area describes a small physical locale within a building,
+ typically a room. HVAC (temperature and humidity) and lighting (room
+ lighting, shades, solar loads) vendors oftentimes deploy area
+ controllers. Area controllers are fed by sensor inputs that monitor
+
+
+
+Martocci, et al. Informational [Page 7]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+ the environmental conditions within the room. Common sensors found
+ in many rooms that feed the area controllers include temperature,
+ occupancy, lighting load, solar load, and relative humidity. Sensors
+ found in specialized rooms (such as chemistry labs) might include air
+ flow, pressure, and CO2 and CO particle sensors. Room actuation
+ includes temperature setpoint, lights, and blinds/curtains.
+
+3.2.3. Zone Controllers
+
+ Zone controllers support a similar set of characteristics to area
+ controllers, albeit for an extended space. A zone is normally a
+ logical grouping or functional division of a commercial building. A
+ zone may also coincidentally map to a physical locale such as a
+ floor.
+
+ Zone controllers may have direct sensor inputs (smoke detectors for
+ fire), controller inputs (room controllers for air handlers in HVAC),
+ or both (door controllers and tamper sensors for security). Like
+ area/room controllers, zone controllers are standalone devices that
+ operate independently or may be attached to the larger network for
+ more synergistic control.
+
+3.3. Equipment Installation Methods
+
+ A BMS is installed very differently from most other IT networks. IT
+ networks are typically installed as an overlay onto the existing
+ environment and are installed from the inside out. That is, the
+ network wiring infrastructure is installed; the switches, routers,
+ and servers are connected and made operational; and finally, the
+ endpoints (e.g., PCs, VoIP phones) are added.
+
+ BMSs, on the other hand, are installed from the outside in. That is,
+ the endpoints (thermostats, lights, smoke detectors) are installed in
+ the spaces first; local control is established in each room and
+ tested for proper operation. The individual rooms are later lashed
+ together into a subsystem (e.g., lighting). The individual
+ subsystems (e.g., lighting, HVAC) then coalesce. Later, the entire
+ system may be merged onto the enterprise network.
+
+ The rationale for this is partly due to the different construction
+ trades having access to a building under construction at different
+ times. The sheer size of a building often dictates that even a
+ single trade may have multiple independent teams working
+ simultaneously. Furthermore, the HVAC, lighting, and fire systems
+ must be fully operational before the building can obtain its
+ occupancy permit. Hence, the BMS must be in place and configured
+ well before any of the IT servers (DHCP; Authentication,
+ Authorization, and Accounting (AAA); DNS; etc.) are operational.
+
+
+
+Martocci, et al. Informational [Page 8]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+ This implies that the BMS cannot rely on the availability of the IT
+ network infrastructure or application servers. Rather, the BMS
+ installation should be planned to dovetail into the IT system once
+ the IT system is available for easy migration onto the IT network.
+ Front-end planning of available switch ports, cable runs, access
+ point (AP) placement, firewalls, and security policies will
+ facilitate this adoption.
+
+3.4. Device Density
+
+ Device density differs, depending on the application and as dictated
+ by the local building code requirements. The following subsections
+ detail typical installation densities for different applications.
+
+3.4.1. HVAC Device Density
+
+ HVAC room applications typically have sensors/actuators and
+ controllers spaced about 50 ft. apart. In most cases, there is a 3:1
+ ratio of sensors/actuators to controllers. That is, for each room
+ there is an installed temperature sensor, flow sensor, and damper
+ actuator for the associated room controller.
+
+ HVAC equipment room applications are quite different. An air handler
+ system may have a single controller with up to 25 sensors and
+ actuators within 50 ft. of the air handler. A chiller or boiler is
+ also controlled with a single equipment controller instrumented with
+ 25 sensors and actuators. Each of these devices would be
+ individually addressed since the devices are mandated or optional as
+ defined by the specified HVAC application. Air handlers typically
+ serve one or two floors of the building. Chillers and boilers may be
+ installed per floor, but many times they service a wing, building, or
+ the entire complex via a central plant.
+
+ These numbers are typical. In special cases, such as clean rooms,
+ operating rooms, pharmaceutical facilities, and labs, the ratio of
+ sensors to controllers can increase by a factor of three. Tenant
+ installations such as malls would opt for packaged units where much
+ of the sensing and actuation is integrated into the unit; here, a
+ single device address would serve the entire unit.
+
+3.4.2. Fire Device Density
+
+ Fire systems are much more uniformly installed, with smoke detectors
+ installed about every 50 ft. This is dictated by local building
+ codes. Fire pull boxes are installed uniformly about every 150 ft.
+ A fire controller will service a floor or wing. The fireman's fire
+ panel will service the entire building and typically is installed in
+ the atrium.
+
+
+
+Martocci, et al. Informational [Page 9]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+3.4.3. Lighting Device Density
+
+ Lighting is also very uniformly installed, with ballasts installed
+ approximately every 10 ft. A lighting panel typically serves 48 to
+ 64 zones. Wired systems tether many lights together into a single
+ zone. Wireless systems configure each fixture independently to
+ increase flexibility and reduce installation costs.
+
+3.4.4. Physical Security Device Density
+
+ Security systems are non-uniformly oriented, with heavy density near
+ doors and windows and lighter density in the building's interior
+ space.
+
+ The recent influx of interior and perimeter camera systems is
+ increasing the security footprint. These cameras are atypical
+ endpoints requiring up to 1 megabit/second (Mbit/s) data rates per
+ camera, as contrasted by the few kbit/s needed by most other BMS
+ sensing equipment. Previously, camera systems had been deployed on
+ proprietary wired high-speed networks. More recent implementations
+ utilize wired or wireless IP cameras integrated into the enterprise
+ LAN.
+
+4. Traffic Pattern
+
+ The independent nature of the automation subsystems within a building
+ can significantly affect network traffic patterns. Much of the real-
+ time sensor environmental data and actuator control stays within the
+ local LLN environment, while alarms and other event data will
+ percolate to higher layers.
+
+ Each sensor in the LLN unicasts point to point (P2P) about 200 bytes
+ of sensor data to its associated controller each minute and expects
+ an application acknowledgment unicast returned from the destination.
+ Each controller unicasts messages at a nominal rate of 6 kbit/minute
+ to peer or supervisory controllers. Thirty percent of each node's
+ packets are destined for other nodes within the LLN. Seventy percent
+ of each node's packets are destined for an aggregation device
+ (multipoint to point (MP2P)) and routed off the LLN. These messages
+ also require a unicast acknowledgment from the destination. The
+ above values assume direct node-to-node communication; meshing and
+ error retransmissions are not considered.
+
+ Multicasts (point to multipoint (P2MP)) to all nodes in the LLN occur
+ for node and object discovery when the network is first commissioned.
+ This data is typically a one-time bind that is henceforth persisted.
+ Lighting systems will also readily use multicasting during normal
+ operations to turn banks of lights "on" and "off" simultaneously.
+
+
+
+Martocci, et al. Informational [Page 10]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+ BMSs may be either polled or event-based. Polled data systems will
+ generate a uniform and constant packet load on the network. Polled
+ architectures, however, have proven not to be scalable. Today, most
+ vendors have developed event-based systems that pass data on event.
+ These systems are highly scalable and generate low data on the
+ network at quiescence. Unfortunately, the systems will generate a
+ heavy load on startup since all initial sensor data must migrate to
+ the controller level. They also will generate a temporary but heavy
+ load during firmware upgrades. This latter load can normally be
+ mitigated by performing these downloads during off-peak hours.
+
+ Devices will also need to reference peers periodically for sensor
+ data or to coordinate operation across systems. Normally, though,
+ data will migrate from the sensor level upwards through the local and
+ area levels, and then to the supervisory level. Traffic bottlenecks
+ will typically form at the funnel point from the area controllers to
+ the supervisory controllers.
+
+ Initial system startup after a controlled outage or unexpected power
+ failure puts tremendous stress on the network and on the routing
+ algorithms. A BMS is comprised of a myriad of control algorithms at
+ the room, area, zone, and enterprise layers. When these control
+ algorithms are at quiescence, the real-time data rate is small, and
+ the network will not saturate. An overall network traffic load of 6
+ kbit/s is typical at quiescence. However, upon any power loss, the
+ control loops and real-time data quickly atrophy. A short power
+ disruption of only 10 minutes may have a long-term deleterious impact
+ on the building control systems, taking many hours to regain proper
+ control. Control applications that cannot handle this level of
+ disruption (e.g., hospital operating rooms) must be fitted with a
+ secondary power source.
+
+ Power disruptions are unexpected and in most cases will immediately
+ impact lines-powered devices. Power disruptions, however, are
+ transparent to battery-powered devices. These devices will continue
+ to attempt to access the LLN during the outage. Battery-powered
+ devices designed to buffer data that has not been delivered will
+ further stress network operations when power returns.
+
+ Upon restart, lines-powered devices will naturally dither due to
+ primary equipment delays or variance in the device self-tests.
+ However, most lines-powered devices will be ready to access the LLN
+ network within 10 seconds of power-up. Empirical testing indicates
+ that routes acquired during startup will tend to be very oblique
+ since the available neighbor lists are incomplete. This demands an
+ adaptive routing protocol to allow for route optimization as the
+ network stabilizes.
+
+
+
+
+Martocci, et al. Informational [Page 11]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+5. Building Automation Routing Requirements
+
+ Following are the building automation routing requirements for
+ networks used to integrate building sensor, actuator, and control
+ products. These requirements are written not presuming any
+ preordained network topology, physical media (wired), or radio
+ technology (wireless).
+
+5.1. Device and Network Commissioning
+
+ Building control systems typically are installed and tested by
+ electricians having little computer knowledge and no network
+ communication knowledge whatsoever. These systems are often
+ installed during the building construction phase, before the drywall
+ and ceilings are in place. For new construction projects, the
+ building enterprise IP network is not in place during installation of
+ the building control system. For retrofit applications, the
+ installer will still operate independently from the IP network so as
+ not to affect network operations during the installation phase.
+
+ In traditional wired systems, correct operation of a light
+ switch/ballast pair was as simple as flipping on the light switch.
+ In wireless applications, the tradesperson has to assure the same
+ operation, yet be sure the operation of the light switch is
+ associated with the proper ballast.
+
+ System-level commissioning will later be deployed using a more
+ computer savvy person with access to a commissioning device (e.g., a
+ laptop computer). The completely installed and commissioned
+ enterprise IP network may or may not be in place at this time.
+ Following are the installation routing requirements.
+
+5.1.1. Zero-Configuration Installation
+
+ It MUST be possible to fully commission network devices without
+ requiring any additional commissioning device (e.g., a laptop). From
+ the ROLL perspective, "zero configuration" means that a node can
+ obtain an address and join the network on its own, without human
+ intervention.
+
+5.1.2. Local Testing
+
+ During installation, the room sensors, actuators, and controllers
+ SHOULD be able to route packets amongst themselves and to any other
+ device within the LLN, without requiring any additional routing
+ infrastructure or routing configuration.
+
+
+
+
+
+Martocci, et al. Informational [Page 12]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+5.1.3. Device Replacement
+
+ To eliminate the need to reconfigure the application upon replacing a
+ failed device in the LLN, the replaced device must be able to
+ advertise the old IP address of the failed device in addition to its
+ new IP address. The routing protocols MUST support hosts and routers
+ that advertise multiple IPv6 addresses.
+
+5.2. Scalability
+
+ Building control systems are designed for facilities from 50,000 sq.
+ ft. to 1M+ sq. ft. The networks that support these systems must
+ cost-effectively scale accordingly. In larger facilities,
+ installation may occur simultaneously on various wings or floors, yet
+ the end system must seamlessly merge. Following are the scalability
+ requirements.
+
+5.2.1. Network Domain
+
+ The routing protocol MUST be able to support networks with at least
+ 2,000 nodes, where 1,000 nodes would act as routers and the other
+ 1,000 nodes would be hosts. Subnetworks (e.g., rooms, primary
+ equipment) within the network must support up to 255 sensors and/or
+ actuators.
+
+5.2.2. Peer-to-Peer Communication
+
+ The data domain for commercial BMSs may sprawl across a vast portion
+ of the physical domain. For example, a chiller may reside in the
+ facility's basement due to its size, yet the associated cooling
+ towers will reside on the roof. The cold-water supply and return
+ pipes snake through all of the intervening floors. The feedback
+ control loops for these systems require data from across the
+ facility.
+
+ A network device MUST be able to communicate in an end-to-end manner
+ with any other device on the network. Thus, the routing protocol
+ MUST provide routes between arbitrary hosts within the appropriate
+ administrative domain.
+
+5.3. Mobility
+
+ Most devices are affixed to walls or installed on ceilings within
+ buildings. Hence, the mobility requirements for commercial buildings
+ are few. However, in wireless environments, location tracking of
+ occupants and assets is gaining favor. Asset-tracking applications,
+ such as tracking capital equipment (e.g., wheelchairs) in medical
+
+
+
+
+Martocci, et al. Informational [Page 13]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+ facilities, require monitoring movement with granularity of a minute;
+ however, tracking babies in a pediatric ward would require latencies
+ less than a few seconds.
+
+ The following subsections document the mobility requirements in the
+ routing layer for mobile devices. Note, however, that mobility can
+ be implemented at various layers of the system, and the specific
+ requirements depend on the chosen layer. For instance, some devices
+ may not depend on a static IP address and are capable of re-
+ establishing application-level communications when given a new IP
+ address. Alternatively, mobile IP may be used, or the set of routers
+ in a building may give an impression of a building-wide network and
+ allow devices to retain their addresses regardless of where they are,
+ handling routing between the devices in the background.
+
+5.3.1. Mobile Device Requirements
+
+ To minimize network dynamics, mobile devices while in motion should
+ not be allowed to act as forwarding devices (routers) for other
+ devices in the LLN. Network configuration should allow devices to be
+ configured as routers or hosts.
+
+5.3.1.1. Device Mobility within the LLN
+
+ An LLN typically spans a single floor in a commercial building.
+ Mobile devices may move within this LLN. For example, a wheelchair
+ may be moved from one room on the floor to another room on the same
+ floor.
+
+ A mobile LLN device that moves within the confines of the same LLN
+ SHOULD re-establish end-to-end communication with a fixed device also
+ in the LLN within 5 seconds after it ceases movement. The LLN
+ network convergence time should be less than 10 seconds once the
+ mobile device stops moving.
+
+5.3.1.2. Device Mobility across LLNs
+
+ A mobile device may move across LLNs, such as a wheelchair being
+ moved to a different floor.
+
+ A mobile device that moves outside of its original LLN SHOULD re-
+ establish end-to-end communication with a fixed device also in the
+ new LLN within 10 seconds after the mobile device ceases movement.
+ The network convergence time should be less than 20 seconds once the
+ mobile device stops moving.
+
+
+
+
+
+
+Martocci, et al. Informational [Page 14]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+5.4. Resource Constrained Devices
+
+ Sensing and actuator device processing power and memory may be 4
+ orders of magnitude less (i.e., 10,000x) than many more traditional
+ client devices on an IP network. The routing mechanisms must
+ therefore be tailored to fit these resource constrained devices.
+
+5.4.1. Limited Memory Footprint on Host Devices
+
+ The software size requirement for non-routing devices (e.g., sleeping
+ sensors and actuators) SHOULD be implementable in 8-bit devices with
+ no more than 128 KB of memory.
+
+5.4.2. Limited Processing Power for Routers
+
+ The software size requirements for routing devices (e.g., room
+ controllers) SHOULD be implementable in 8-bit devices with no more
+ than 256 KB of flash memory.
+
+5.4.3. Sleeping Devices
+
+ Sensing devices will, in some cases, utilize battery power or energy
+ harvesting techniques for power and will operate mostly in a sleep
+ mode to maintain power consumption within a modest budget. The
+ routing protocol MUST take into account device characteristics such
+ as power budget.
+
+ Typically, sensor battery life (2,000 mAh) needs to extend for at
+ least 5 years when the device is transmitting its data (200 octets)
+ once per minute over a low-power transceiver (25 mA) and expecting an
+ application acknowledgment. In this case, the transmitting device
+ must leave its receiver in a high-powered state, awaiting the return
+ of the application ACK. To minimize this latency, a highly efficient
+ routing protocol that minimizes hops, and hence end-to-end
+ communication, is required. The routing protocol MUST take into
+ account node properties, such as "low-powered node", that produce
+ efficient low-latency routes that minimize radio "on" time for these
+ devices.
+
+ Sleeping devices MUST be able to receive inbound data. Messages sent
+ to battery-powered nodes MUST be buffered by the last-hop router for
+ a period of at least 20 seconds when the destination node is
+ currently in its sleep cycle.
+
+
+
+
+
+
+
+
+Martocci, et al. Informational [Page 15]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+5.5. Addressing
+
+ Building management systems require different communication schemes
+ to solicit or post network information. Multicasts or anycasts need
+ to be used to decipher unresolved references within a device when the
+ device first joins the network.
+
+ As with any network communication, multicasting should be minimized.
+ This is especially a problem for small embedded devices with limited
+ network bandwidth. Multicasts are typically used for network joins
+ and application binding in embedded systems. Routing MUST support
+ anycast, unicast, and multicast.
+
+5.6. Manageability
+
+ As previously noted in Section 3.3, installation of LLN devices
+ within a BMS follows an "outside-in" work flow. Edge devices are
+ installed first and tested for communication and application
+ integrity. These devices are then aggregated into islands, then
+ LLNs, and later affixed onto the enterprise network.
+
+ The need for diagnostics most often occurs during the installation
+ and commissioning phase, although at times diagnostic information may
+ be requested during normal operation. Battery-powered wireless
+ devices typically will have a self-diagnostic mode that can be
+ initiated via a button press on the device. The device will display
+ its link status and/or end-to-end connectivity when the button is
+ pressed. Lines-powered devices will continuously display
+ communication status via a bank of LEDs, possibly denoting signal
+ strength and end-to-end application connectivity.
+
+ The local diagnostics noted above oftentimes are suitable for
+ defining room-level networks. However, as these devices aggregate,
+ system-level diagnostics may need to be executed to ameliorate route
+ vacillation, excessive hops, communication retries, and/or network
+ bottlenecks.
+
+ In operational networks, due to the mission-critical nature of the
+ application, the LLN devices will be temporally monitored by the
+ higher layers to assure that communication integrity is maintained.
+ Failure to maintain this communication will result in an alarm being
+ forwarded to the enterprise network from the monitoring node for
+ analysis and remediation.
+
+
+
+
+
+
+
+
+Martocci, et al. Informational [Page 16]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+ In addition to the initial installation and commissioning of the
+ system, it is equally important for the ongoing maintenance of the
+ system to be simple and inexpensive. This implies a straightforward
+ device swap when a failed device is replaced, as noted in Section
+ 5.1.3.
+
+5.6.1. Diagnostics
+
+ To improve diagnostics, the routing protocol SHOULD be able to be
+ placed in and out of "verbose" mode. Verbose mode is a temporary
+ debugging mode that provides additional communication information
+ including, at least, the total number of routed packets sent and
+ received, the number of routing failures (no route available),
+ neighbor table members, and routing table entries. The data provided
+ in verbose mode should be sufficient that a network connection graph
+ could be constructed and maintained by the monitoring node.
+
+ Diagnostic data should be kept by the routers continuously and be
+ available for solicitation at any time by any other node on the
+ internetwork. Verbose mode will be activated/deactivated via
+ unicast, multicast, or other means. Devices having available
+ resources may elect to support verbose mode continuously.
+
+5.6.2. Route Tracking
+
+ Route diagnostics SHOULD be supported, providing information such as
+ route quality, number of hops, and available alternate active routes
+ with associated costs. Route quality is the relative measure of
+ "goodness" of the selected source to destination route as compared to
+ alternate routes. This composite value may be measured as a function
+ of hop count, signal strength, available power, existing active
+ routes, or any other criteria deemed by ROLL as the route cost
+ differentiator.
+
+5.7. Route Selection
+
+ Route selection determines reliability and quality of the
+ communication among the devices by optimizing routes over time and
+ resolving any nuances developed at system startup when nodes are
+ asynchronously adding themselves to the network.
+
+5.7.1. Route Cost
+
+ The routing protocol MUST support a metric of route quality and
+ optimize selection according to such metrics within constraints
+ established for links along the routes. These metrics SHOULD reflect
+ metrics such as signal strength, available bandwidth, hop count,
+ energy availability, and communication error rates.
+
+
+
+Martocci, et al. Informational [Page 17]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+5.7.2. Route Adaptation
+
+ Communication routes MUST be adaptive and converge toward optimality
+ of the chosen metric (e.g., signal quality, hop count) in time.
+
+5.7.3. Route Redundancy
+
+ The routing layer SHOULD be configurable to allow secondary and
+ tertiary routes to be established and used upon failure of the
+ primary route.
+
+5.7.4. Route Discovery Time
+
+ Mission-critical commercial applications (e.g., fire, security)
+ require reliable communication and guaranteed end-to-end delivery of
+ all messages in a timely fashion. Application-layer time-outs must
+ be selected judiciously to cover anomalous conditions such as lost
+ packets and/or route discoveries, yet not be set too large to over-
+ damp the network response. If route discovery occurs during packet
+ transmission time (reactive routing), it SHOULD NOT add more than 120
+ ms of latency to the packet delivery time.
+
+5.7.5. Route Preference
+
+ The routing protocol SHOULD allow for the support of manually
+ configured static preferred routes.
+
+5.7.6. Real-Time Performance Measures
+
+ A node transmitting a "request with expected reply" to another node
+ must send the message to the destination and receive the response in
+ not more than 120 ms. This response time should be achievable with 5
+ or less hops in each direction. This requirement assumes network
+ quiescence and a negligible turnaround time at the destination node.
+
+5.7.7. Prioritized Routing
+
+ Network and application packet routing prioritization must be
+ supported to assure that mission-critical applications (e.g., fire
+ detection) cannot be deferred while less critical applications access
+ the network. The routing protocol MUST be able to provide routes
+ with different characteristics, also referred to as Quality of
+ Service (QoS) routing.
+
+
+
+
+
+
+
+
+Martocci, et al. Informational [Page 18]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+5.8. Security Requirements
+
+ This section sets forth specific requirements that are placed on any
+ protocols developed or used in the ROLL building environment, in
+ order to ensure adequate security and retain suitable flexibility of
+ use and function of the protocol.
+
+ Due to the variety of buildings and tenants, the BMSs must be
+ completely configurable on-site.
+
+ Due to the quantity of the BMS devices (thousands) and their
+ inaccessibility (oftentimes above ceilings), security configuration
+ over the network is preferred over local configuration.
+
+ Wireless encryption and device authentication security policies need
+ to be considered in commercial buildings, while keeping in mind the
+ impact on the limited processing capabilities and additional latency
+ incurred on the sensors, actuators, and controllers.
+
+ BMSs are typically highly configurable in the field, and hence the
+ security policy is most often dictated by the type of building to
+ which the BMS is being installed. Single-tenant owner-occupied
+ office buildings installing lighting or HVAC control are candidates
+ for implementing a low level of security on the LLN, especially when
+ the LLN is not connected to an external network. Antithetically,
+ military or pharmaceutical facilities require strong security
+ policies. As noted in the installation procedures described in
+ Sections 3.3 and 5.2, security policies MUST support dynamic
+ configuration to allow for a low level of security during the
+ installation phase (prior to building occupancy, when it may be
+ appropriate to use only diagnostic levels of security), yet to make
+ it possible to easily raise the security level network-wide during
+ the commissioning phase of the system.
+
+5.8.1. Building Security Use Case
+
+ LLNs for commercial building applications should always implement and
+ use encrypted packets. However, depending on the state of the LLN,
+ the security keys may either be:
+
+ 1) a key obtained from a trust center already operable on the LLN;
+
+ 2) a pre-shared static key as defined by the general contractor or
+ its designee; or
+
+ 3) a well-known default static key.
+
+
+
+
+
+Martocci, et al. Informational [Page 19]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+ Unless a node entering the network had previously received its
+ credentials from the trust center, the entering node will try to
+ solicit the trust center for the network key. If the trust center is
+ accessible, the trust center will MAC-authenticate the entering node
+ and return the security keys. If the trust center is not available,
+ the entering node will check to determine if it has been given a
+ network key by an off-band means and use it to access the network.
+ If no network key has been configured in the device, it will revert
+ to the default network key and enter the network. If neither of
+ these keys were valid, the device would signal via a fault LED.
+
+ This approach would allow for independent simplified commissioning,
+ yet centralized authentication. The building owner or building type
+ would then dictate when the trust center would be deployed. In many
+ cases, the trust center need not be deployed until all of the local
+ room commissioning is complete. Yet, at the province of the owner,
+ the trust center may be deployed from the onset, thereby trading
+ installation and commissioning flexibility for tighter security.
+
+5.8.2. Authentication
+
+ Authentication SHOULD be optional on the LLN. Authentication SHOULD
+ be fully configurable on-site. Authentication policy and updates
+ MUST be routable over-the-air. Authentication SHOULD occur upon
+ joining or rejoining a network. However, once authenticated, devices
+ SHOULD NOT need to reauthenticate with any other devices in the LLN.
+ Packets may need authentication at the source and destination nodes;
+ however, packets routed through intermediate hops should not need
+ reauthentication at each hop.
+
+ These requirements mean that at least one LLN routing protocol
+ solution specification MUST include support for authentication.
+
+5.8.3. Encryption
+
+5.8.3.1. Encryption Types
+
+ Data encryption of packets MUST be supported by all protocol solution
+ specifications. Support can be provided by use of a network-wide key
+ and/or an application key. The network key would apply to all
+ devices in the LLN. The application key would apply to a subset of
+ devices in the LLN.
+
+ The network key and application key would be mutually exclusive. The
+ routing protocol MUST allow routing a packet encrypted with an
+ application key through forwarding devices without requiring each
+ node in the route to have the application key.
+
+
+
+
+Martocci, et al. Informational [Page 20]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+5.8.3.2. Packet Encryption
+
+ The encryption policy MUST support either encryption of the payload
+ only or of the entire packet. Payload-only encryption would
+ eliminate the decryption/re-encryption overhead at every hop,
+ providing more real-time performance.
+
+5.8.4. Disparate Security Policies
+
+ Due to the limited resources of an LLN, the security policy defined
+ within the LLN MUST be able to differ from that of the rest of the IP
+ network within the facility, yet packets MUST still be able to route
+ to or through the LLN from/to these networks.
+
+5.8.5. Routing Security Policies to Sleeping Devices
+
+ The routing protocol MUST gracefully handle routing temporal security
+ updates (e.g., dynamic keys) to sleeping devices on their "awake"
+ cycle to assure that sleeping devices can readily and efficiently
+ access the network.
+
+6. Security Considerations
+
+ The requirements placed on the LLN routing protocol in order to
+ provide the correct level of security support are presented in
+ Section 5.8.
+
+ LLNs deployed in a building environment may be entirely isolated from
+ other networks, attached to normal IP networks within the building
+ yet physically disjoint from the wider Internet, or connected either
+ directly or through other IP networks to the Internet. Additionally,
+ even where no wired connectivity exists outside of the building, the
+ use of wireless infrastructure within the building means that
+ physical connectivity to the LLN is possible for an attacker.
+
+ Therefore, it is important that any routing protocol solution
+ designed to meet the requirements included in this document addresses
+ the security features requirements described in Section 5.8.
+ Implementations of these protocols will be required in the protocol
+ specifications to provide the level of support indicated in Section
+ 5.8, and will be encouraged to make the support flexibly configurable
+ to enable an operator to make a judgment of the level of security
+ that they want to deploy at any time.
+
+ As noted in Section 5.8, use/deployment of the different security
+ features is intended to be optional. This means that, although the
+ protocols developed must conform to the requirements specified, the
+ operator is free to determine the level of risk and the trade-offs
+
+
+
+Martocci, et al. Informational [Page 21]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+ against performance. An implementation must not make those choices
+ on behalf of the operator by avoiding implementing any mandatory-to-
+ implement security features.
+
+ This informational requirements specification introduces no new
+ security concerns.
+
+7. Acknowledgments
+
+ In addition to the authors, JP. Vasseur, David Culler, Ted Humpal,
+ and Zach Shelby are gratefully acknowledged for their contributions
+ to this document.
+
+8. References
+
+8.1. Normative References
+
+ [RFC2119] Bradner, S., "Key words for use in RFCs to Indicate
+ Requirement Levels", BCP 14, RFC 2119, March 1997.
+
+8.2. Informative References
+
+ [ROLL-TERM] Vasseur, JP., "Terminology in Low power And Lossy
+ Networks", Work in Progress, March 2010.
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+Martocci, et al. Informational [Page 22]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+Appendix A. Additional Building Requirements
+
+ Appendix A contains additional building requirements that were deemed
+ out of scope for ROLL, yet provided ancillary substance for the
+ reader.
+
+A.1. Additional Commercial Product Requirements
+
+A.1.1. Wired and Wireless Implementations
+
+ Vendors will likely not develop a separate product line for both
+ wired and wireless networks. Hence, the solutions set forth must
+ support both wired and wireless implementations.
+
+A.1.2. World-Wide Applicability
+
+ Wireless devices must be supportable unlicensed bands.
+
+A.2. Additional Installation and Commissioning Requirements
+
+A.2.1. Unavailability of an IP Network
+
+ Product commissioning must be performed by an application engineer
+ prior to the installation of the IP network (e.g., switches, routers,
+ DHCP, DNS).
+
+A.3. Additional Network Requirements
+
+A.3.1. TCP/UDP
+
+ Connection-based and connectionless services must be supported.
+
+A.3.2. Interference Mitigation
+
+ The network must automatically detect interference and seamlessly
+ switch the channel to improve communication. Channel changes, and
+ the nodes' responses to a given channel change, must occur within 60
+ seconds.
+
+
+
+
+
+
+
+
+
+
+
+
+
+Martocci, et al. Informational [Page 23]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+A.3.3. Packet Reliability
+
+ In building automation, it is required that the network meet the
+ following minimum criteria:
+
+ <1% MAC-layer errors on all messages, after no more than three
+ retries;
+
+ <0.1% network-layer errors on all messages, after no more than three
+ additional retries;
+
+ <0.01% application-layer errors on all messages.
+
+ Therefore, application-layer messages will fail no more than once
+ every 100,000 messages.
+
+A.3.4. Merging Commissioned Islands
+
+ Subsystems are commissioned by various vendors at various times
+ during building construction. These subnetworks must seamlessly
+ merge into networks and networks must seamlessly merge into
+ internetworks since the end user wants a holistic view of the system.
+
+A.3.5. Adjustable Routing Table Sizes
+
+ The routing protocol must allow constrained nodes to hold an
+ abbreviated set of routes. That is, the protocol should not mandate
+ that the node routing tables be exhaustive.
+
+A.3.6. Automatic Gain Control
+
+ For wireless implementations, the device radios should incorporate
+ automatic transmit power regulation to maximize packet transfer and
+ minimize network interference, regardless of network size or density.
+
+A.3.7. Device and Network Integrity
+
+ Commercial-building devices must all be periodically scanned to
+ assure that each device is viable and can communicate data and alarm
+ information as needed. Routers should maintain previous packet flow
+ information temporally to minimize overall network overhead.
+
+A.4. Additional Performance Requirements
+
+A.4.1. Data Rate Performance
+
+ An effective data rate of 20 kbit/s is the lowest acceptable
+ operational data rate on the network.
+
+
+
+Martocci, et al. Informational [Page 24]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+A.4.2. Firmware Upgrades
+
+ To support high-speed code downloads, routing should support
+ transports that provide parallel downloads to targeted devices, yet
+ guarantee packet delivery. In cases where the spatial position of
+ the devices requires multiple hops, the algorithm should recurse
+ through the network until all targeted devices have been serviced.
+ Devices receiving a download may cease normal operation, but upon
+ completion of the download must automatically resume normal
+ operation.
+
+A.4.3. Route Persistence
+
+ To eliminate high network traffic in power-fail or brown-out
+ conditions, previously established routes should be remembered and
+ invoked prior to establishing new routes for those devices re-
+ entering the network.
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+Martocci, et al. Informational [Page 25]
+
+RFC 5867 Building Automation Routing Requirements in LLNs June 2010
+
+
+Authors' Addresses
+
+ Jerry Martocci
+ Johnson Controls Inc.
+ 507 E. Michigan Street
+ Milwaukee, WI 53202
+ USA
+ Phone: +1 414 524 4010
+ EMail: jerald.p.martocci@jci.com
+
+
+ Pieter De Mil
+ Ghent University - IBCN
+ G. Crommenlaan 8 bus 201
+ Ghent 9050
+ Belgium
+ Phone: +32 9331 4981
+ Fax: +32 9331 4899
+ EMail: pieter.demil@intec.ugent.be
+
+
+ Nicolas Riou
+ Schneider Electric
+ Technopole 38TEC T3
+ 37 quai Paul Louis Merlin
+ 38050 Grenoble Cedex 9
+ France
+ Phone: +33 4 76 57 66 15
+ EMail: nicolas.riou@fr.schneider-electric.com
+
+
+ Wouter Vermeylen
+ Arts Centre Vooruit
+ Ghent 9000
+ Belgium
+ EMail: wouter@vooruit.be
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+Martocci, et al. Informational [Page 26]
+