+Internet Engineering Task Force (IETF) M. Lasserre
+Request for Comments: 7365 F. Balus
+Category: Informational Alcatel-Lucent
+ISSN: 2070-1721 T. Morin
+ Orange
+ N. Bitar
+ Verizon
+ Y. Rekhter
+ Juniper
+ October 2014
+
+
+ Framework for Data Center (DC) Network Virtualization
+
+Abstract
+
+ This document provides a framework for Data Center (DC) Network
+ Virtualization over Layer 3 (NVO3) and defines a reference model
+ along with logical components required to design a solution.
+
+Status of This Memo
+
+ This document is not an Internet Standards Track specification; it is
+ published for informational purposes.
+
+ This document is a product of the Internet Engineering Task Force
+ (IETF). It represents the consensus of the IETF community. It has
+ received public review and has been approved for publication by the
+ Internet Engineering Steering Group (IESG). Not all documents
+ approved by the IESG are a candidate for any level of Internet
+ Standard; see Section 2 of RFC 5741.
+
+ Information about the current status of this document, any errata,
+ and how to provide feedback on it may be obtained at
+ http://www.rfc-editor.org/info/rfc7365.
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+Lasserre, et al. Informational [Page 1]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+Copyright Notice
+
+ Copyright (c) 2014 IETF Trust and the persons identified as the
+ document authors. All rights reserved.
+
+ This document is subject to BCP 78 and the IETF Trust's Legal
+ Provisions Relating to IETF Documents
+ (http://trustee.ietf.org/license-info) in effect on the date of
+ publication of this document. Please review these documents
+ carefully, as they describe your rights and restrictions with respect
+ to this document. Code Components extracted from this document must
+ include Simplified BSD License text as described in Section 4.e of
+ the Trust Legal Provisions and are provided without warranty as
+ described in the Simplified BSD License.
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+Lasserre, et al. Informational [Page 2]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+Table of Contents
+
+ 1. Introduction ....................................................4
+ 1.1. General Terminology ........................................4
+ 1.2. DC Network Architecture ....................................7
+ 2. Reference Models ................................................8
+ 2.1. Generic Reference Model ....................................8
+ 2.2. NVE Reference Model .......................................10
+ 2.3. NVE Service Types .........................................11
+ 2.3.1. L2 NVE Providing Ethernet LAN-Like Service .........11
+ 2.3.2. L3 NVE Providing IP/VRF-Like Service ...............11
+ 2.4. Operational Management Considerations .....................12
+ 3. Functional Components ..........................................12
+ 3.1. Service Virtualization Components .........................12
+ 3.1.1. Virtual Access Points (VAPs) .......................12
+ 3.1.2. Virtual Network Instance (VNI) .....................12
+ 3.1.3. Overlay Modules and VN Context .....................14
+ 3.1.4. Tunnel Overlays and Encapsulation Options ..........14
+ 3.1.5. Control-Plane Components ...........................14
+ 3.1.5.1. Distributed vs. Centralized
+ Control Plane .............................14
+ 3.1.5.2. Auto-provisioning and Service Discovery ...15
+ 3.1.5.3. Address Advertisement and Tunnel Mapping ..15
+ 3.1.5.4. Overlay Tunneling .........................16
+ 3.2. Multihoming ...............................................16
+ 3.3. VM Mobility ...............................................17
+ 4. Key Aspects of Overlay Networks ................................17
+ 4.1. Pros and Cons .............................................18
+ 4.2. Overlay Issues to Consider ................................19
+ 4.2.1. Data Plane vs. Control Plane Driven ................19
+ 4.2.2. Coordination between Data Plane and Control Plane ..19
+ 4.2.3. Handling Broadcast, Unknown Unicast, and
+ Multicast (BUM) Traffic ............................20
+ 4.2.4. Path MTU ...........................................20
+ 4.2.5. NVE Location Trade-Offs ............................21
+ 4.2.6. Interaction between Network Overlays and
+ Underlays ..........................................22
+ 5. Security Considerations ........................................22
+ 6. Informative References .........................................24
+ Acknowledgments ...................................................26
+ Authors' Addresses ................................................26
+
+
+
+
+
+
+
+
+
+
+Lasserre, et al. Informational [Page 3]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+1. Introduction
+
+ This document provides a framework for Data Center (DC) Network
+ Virtualization over Layer 3 (NVO3) tunnels. This framework is
+ intended to aid in standardizing protocols and mechanisms to support
+ large-scale network virtualization for data centers.
+
+ [RFC7364] defines the rationale for using overlay networks in order
+ to build large multi-tenant data center networks. Compute, storage
+ and network virtualization are often used in these large data centers
+ to support a large number of communication domains and end systems.
+
+ This document provides reference models and functional components of
+ data center overlay networks as well as a discussion of technical
+ issues that have to be addressed.
+
+1.1. General Terminology
+
+ This document uses the following terminology:
+
+ NVO3 Network: An overlay network that provides a Layer 2 (L2) or
+ Layer 3 (L3) service to Tenant Systems over an L3 underlay network
+ using the architecture and protocols as defined by the NVO3 Working
+ Group.
+
+ Network Virtualization Edge (NVE): An NVE is the network entity that
+ sits at the edge of an underlay network and implements L2 and/or L3
+ network virtualization functions. The network-facing side of the NVE
+ uses the underlying L3 network to tunnel tenant frames to and from
+ other NVEs. The tenant-facing side of the NVE sends and receives
+ Ethernet frames to and from individual Tenant Systems. An NVE could
+ be implemented as part of a virtual switch within a hypervisor, a
+ physical switch or router, or a Network Service Appliance, or it
+ could be split across multiple devices.
+
+ Virtual Network (VN): A VN is a logical abstraction of a physical
+ network that provides L2 or L3 network services to a set of Tenant
+ Systems. A VN is also known as a Closed User Group (CUG).
+
+ Virtual Network Instance (VNI): A specific instance of a VN from the
+ perspective of an NVE.
+
+ Virtual Network Context (VN Context) Identifier: Field in an overlay
+ encapsulation header that identifies the specific VN the packet
+ belongs to. The egress NVE uses the VN Context identifier to deliver
+ the packet to the correct Tenant System. The VN Context identifier
+ can be a locally significant identifier or a globally unique
+ identifier.
+
+
+
+Lasserre, et al. Informational [Page 4]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+ Underlay or Underlying Network: The network that provides the
+ connectivity among NVEs and that NVO3 packets are tunneled over,
+ where an NVO3 packet carries an NVO3 overlay header followed by a
+ tenant packet. The underlay network does not need to be aware that
+ it is carrying NVO3 packets. Addresses on the underlay network
+ appear as "outer addresses" in encapsulated NVO3 packets. In
+ general, the underlay network can use a completely different protocol
+ (and address family) from that of the overlay. In the case of NVO3,
+ the underlay network is IP.
+
+ Data Center (DC): A physical complex housing physical servers,
+ network switches and routers, network service appliances, and
+ networked storage. The purpose of a data center is to provide
+ application, compute, and/or storage services. One such service is
+ virtualized infrastructure data center services, also known as
+ "Infrastructure as a Service".
+
+ Virtual Data Center (Virtual DC): A container for virtualized
+ compute, storage, and network services. A virtual DC is associated
+ with a single tenant and can contain multiple VNs and Tenant Systems
+ connected to one or more of these VNs.
+
+ Virtual Machine (VM): A software implementation of a physical machine
+ that runs programs as if they were executing on a physical, non-
+ virtualized machine. Applications (generally) do not know they are
+ running on a VM as opposed to running on a "bare metal" host or
+ server, though some systems provide a para-virtualization environment
+ that allows an operating system or application to be aware of the
+ presence of virtualization for optimization purposes.
+
+ Hypervisor: Software running on a server that allows multiple VMs to
+ run on the same physical server. The hypervisor manages and provides
+ shared computation, memory, and storage services and network
+ connectivity to the VMs that it hosts. Hypervisors often embed a
+ virtual switch (see below).
+
+ Server: A physical end-host machine that runs user applications. A
+ standalone (or "bare metal") server runs a conventional operating
+ system hosting a single-tenant application. A virtualized server
+ runs a hypervisor supporting one or more VMs.
+
+ Virtual Switch (vSwitch): A function within a hypervisor (typically
+ implemented in software) that provides similar forwarding services to
+ a physical Ethernet switch. A vSwitch forwards Ethernet frames
+ between VMs running on the same server or between a VM and a physical
+ Network Interface Card (NIC) connecting the server to a physical
+ Ethernet switch or router. A vSwitch also enforces network isolation
+ between VMs that by policy are not permitted to communicate with each
+
+
+
+Lasserre, et al. Informational [Page 5]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+ other (e.g., by honoring VLANs). A vSwitch may be bypassed when an
+ NVE is enabled on the host server.
+
+ Tenant: The customer using a virtual network and any associated
+ resources (e.g., compute, storage, and network). A tenant could be
+ an enterprise or a department/organization within an enterprise.
+
+ Tenant System: A physical or virtual system that can play the role of
+ a host or a forwarding element such as a router, switch, firewall,
+ etc. It belongs to a single tenant and connects to one or more VNs
+ of that tenant.
+
+ Tenant Separation: Refers to isolating traffic of different tenants
+ such that traffic from one tenant is not visible to or delivered to
+ another tenant, except when allowed by policy. Tenant separation
+ also refers to address space separation, whereby different tenants
+ can use the same address space without conflict.
+
+ Virtual Access Points (VAPs): A logical connection point on the NVE
+ for connecting a Tenant System to a virtual network. Tenant Systems
+ connect to VNIs at an NVE through VAPs. VAPs can be physical ports
+ or virtual ports identified through logical interface identifiers
+ (e.g., VLAN ID or internal vSwitch Interface ID connected to a VM).
+
+ End Device: A physical device that connects directly to the DC
+ underlay network. This is in contrast to a Tenant System, which
+ connects to a corresponding tenant VN. An End Device is administered
+ by the DC operator rather than a tenant and is part of the DC
+ infrastructure. An End Device may implement NVO3 technology in
+ support of NVO3 functions. Examples of an End Device include hosts
+ (e.g., server or server blade), storage systems (e.g., file servers
+ and iSCSI storage systems), and network devices (e.g., firewall,
+ load-balancer, and IPsec gateway).
+
+ Network Virtualization Authority (NVA): Entity that provides
+ reachability and forwarding information to NVEs.
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+Lasserre, et al. Informational [Page 6]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+1.2. DC Network Architecture
+
+ A generic architecture for data centers is depicted in Figure 1:
+
+ ,---------.
+ ,' `.
+ ( IP/MPLS WAN )
+ `. ,'
+ `-+------+'
+ \ /
+ +--------+ +--------+
+ | DC |+-+| DC |
+ |gateway |+-+|gateway |
+ +--------+ +--------+
+ | /
+ .--. .--.
+ ( ' '.--.
+ .-.' Intra-DC '
+ ( network )
+ ( .'-'
+ '--'._.'. )\ \
+ / / '--' \ \
+ / / | | \ \
+ +--------+ +--------+ +--------+
+ | access | | access | | access |
+ | switch | | switch | | switch |
+ +--------+ +--------+ +--------+
+ / \ / \ / \
+ __/_ \ / \ /_ _\__
+ '--------' '--------' '--------' '--------'
+ : End : : End : : End : : End :
+ : Device : : Device : : Device : : Device :
+ '--------' '--------' '--------' '--------'
+
+ Figure 1: A Generic Architecture for Data Centers
+
+ An example of multi-tier DC network architecture is presented in
+ Figure 1. It provides a view of the physical components inside a DC.
+
+ A DC network is usually composed of intra-DC networks and network
+ services, and inter-DC network and network connectivity services.
+
+ DC networking elements can act as strict L2 switches and/or provide
+ IP routing capabilities, including network service virtualization.
+
+ In some DC architectures, some tier layers could provide L2 and/or L3
+ services. In addition, some tier layers may be collapsed, and
+ Internet connectivity, inter-DC connectivity, and VPN support may be
+
+
+
+Lasserre, et al. Informational [Page 7]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+ handled by a smaller number of nodes. Nevertheless, one can assume
+ that the network functional blocks in a DC fit in the architecture
+ depicted in Figure 1.
+
+ The following components can be present in a DC:
+
+ - Access switch: Hardware-based Ethernet switch aggregating all
+ Ethernet links from the End Devices in a rack representing the
+ entry point in the physical DC network for the hosts. It may also
+ provide routing functionality, virtual IP network connectivity, or
+ Layer 2 tunneling over IP, for instance. Access switches are
+ usually multihomed to aggregation switches in the Intra-DC
+ network. A typical example of an access switch is a Top-of-Rack
+ (ToR) switch. Other deployment scenarios may use an intermediate
+ Blade Switch before the ToR, or an End-of-Row (EoR) switch, to
+ provide similar functions to a ToR.
+
+ - Intra-DC Network: Network composed of high-capacity core nodes
+ (Ethernet switches/routers). Core nodes may provide virtual
+ Ethernet bridging and/or IP routing services.
+
+ - DC Gateway (DC GW): Gateway to the outside world providing DC
+ interconnect and connectivity to Internet and VPN customers. In
+ the current DC network model, this may be simply a router
+ connected to the Internet and/or an IP VPN/L2VPN PE. Some network
+ implementations may dedicate DC GWs for different connectivity
+ types (e.g., a DC GW for Internet and another for VPN).
+
+ Note that End Devices may be single-homed or multihomed to access
+ switches.
+
+2. Reference Models
+
+2.1. Generic Reference Model
+
+ Figure 2 depicts a DC reference model for network virtualization
+ overlays where NVEs provide a logical interconnect between Tenant
+ Systems that belong to a specific VN.
+
+
+
+
+
+
+
+
+
+
+
+
+
+Lasserre, et al. Informational [Page 8]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+ +--------+ +--------+
+ | Tenant +--+ +----| Tenant |
+ | System | | (') | System |
+ +--------+ | ................. ( ) +--------+
+ | +---+ +---+ (_)
+ +--|NVE|---+ +---|NVE|-----+
+ +---+ | | +---+
+ / . +-----+ .
+ / . +--| NVA |--+ .
+ / . | +-----+ \ .
+ | . | \ .
+ | . | Overlay +--+--++--------+
+ +--------+ | . | Network | NVE || Tenant |
+ | Tenant +--+ . | | || System |
+ | System | . \ +---+ +--+--++--------+
+ +--------+ .....|NVE|.........
+ +---+
+ |
+ |
+ =====================
+ | |
+ +--------+ +--------+
+ | Tenant | | Tenant |
+ | System | | System |
+ +--------+ +--------+
+
+ Figure 2: Generic Reference Model for DC Network Virtualization
+ Overlays
+
+ In order to obtain reachability information, NVEs may exchange
+ information directly between themselves via a control-plane protocol.
+ In this case, a control-plane module resides in every NVE.
+
+ It is also possible for NVEs to communicate with an external Network
+ Virtualization Authority (NVA) to obtain reachability and forwarding
+ information. In this case, a protocol is used between NVEs and
+ NVA(s) to exchange information.
+
+ It should be noted that NVAs may be organized in clusters for
+ redundancy and scalability and can appear as one logically
+ centralized controller. In this case, inter-NVA communication is
+ necessary to synchronize state among nodes within a cluster or share
+ information across clusters. The information exchanged between NVAs
+ of the same cluster could be different from the information exchanged
+ across clusters.
+
+
+
+
+
+
+Lasserre, et al. Informational [Page 9]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+ A Tenant System can be attached to an NVE in several ways:
+
+ - locally, by being co-located in the same End Device
+
+ - remotely, via a point-to-point connection or a switched network
+
+ When an NVE is co-located with a Tenant System, the state of the
+ Tenant System can be determined without protocol assistance. For
+ instance, the operational status of a VM can be communicated via a
+ local API. When an NVE is remotely connected to a Tenant System, the
+ state of the Tenant System or NVE needs to be exchanged directly or
+ via a management entity, using a control-plane protocol or API, or
+ directly via a data-plane protocol.
+
+ The functional components in Figure 2 do not necessarily map directly
+ to the physical components described in Figure 1. For example, an
+ End Device can be a server blade with VMs and a virtual switch. A VM
+ can be a Tenant System, and the NVE functions may be performed by the
+ host server. In this case, the Tenant System and NVE function are
+ co-located. Another example is the case where the End Device is the
+ Tenant System and the NVE function can be implemented by the
+ connected ToR. In this case, the Tenant System and NVE function are
+ not co-located.
+
+ Underlay nodes utilize L3 technologies to interconnect NVE nodes.
+ These nodes perform forwarding based on outer L3 header information,
+ and generally do not maintain state for each tenant service, albeit
+ some applications (e.g., multicast) may require control-plane or
+ forwarding-plane information that pertains to a tenant, group of
+ tenants, tenant service, or a set of services that belong to one or
+ more tenants. Mechanisms to control the amount of state maintained
+ in the underlay may be needed.
+
+2.2. NVE Reference Model
+
+ Figure 3 depicts the NVE reference model. One or more VNIs can be
+ instantiated on an NVE. A Tenant System interfaces with a
+ corresponding VNI via a VAP. An overlay module provides tunneling
+ overlay functions (e.g., encapsulation and decapsulation of tenant
+ traffic, tenant identification, and mapping, etc.).
+
+
+
+
+
+
+
+
+
+
+
+Lasserre, et al. Informational [Page 10]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+ +-------- L3 Network -------+
+ | |
+ | Tunnel Overlay |
+ +------------+---------+ +---------+------------+
+ | +----------+-------+ | | +---------+--------+ |
+ | | Overlay Module | | | | Overlay Module | |
+ | +---------+--------+ | | +---------+--------+ |
+ | |VN Context| | VN Context| |
+ | | | | | |
+ | +--------+-------+ | | +--------+-------+ |
+ | | |VNI| . |VNI| | | | |VNI| . |VNI| |
+ NVE1 | +-+------------+-+ | | +-+-----------+--+ | NVE2
+ | | VAPs | | | | VAPs | |
+ +----+------------+----+ +----+-----------+-----+
+ | | | |
+ | | | |
+ Tenant Systems Tenant Systems
+
+ Figure 3: Generic NVE Reference Model
+
+ Note that some NVE functions (e.g., data-plane and control-plane
+ functions) may reside in one device or may be implemented separately
+ in different devices.
+
+2.3. NVE Service Types
+
+ An NVE provides different types of virtualized network services to
+ multiple tenants, i.e., an L2 service or an L3 service. Note that an
+ NVE may be capable of providing both L2 and L3 services for a tenant.
+ This section defines the service types and associated attributes.
+
+2.3.1. L2 NVE Providing Ethernet LAN-Like Service
+
+ An L2 NVE implements Ethernet LAN emulation, an Ethernet-based
+ multipoint service similar to an IETF Virtual Private LAN Service
+ (VPLS) [RFC4761][RFC4762] or Ethernet VPN [EVPN] service, where the
+ Tenant Systems appear to be interconnected by a LAN environment over
+ an L3 overlay. As such, an L2 NVE provides per-tenant virtual
+ switching instance (L2 VNI) and L3 (IP/MPLS) tunneling encapsulation
+ of tenant Media Access Control (MAC) frames across the underlay.
+ Note that the control plane for an L2 NVE could be implemented
+ locally on the NVE or in a separate control entity.
+
+2.3.2. L3 NVE Providing IP/VRF-Like Service
+
+ An L3 NVE provides virtualized IP forwarding service, similar to IETF
+ IP VPN (e.g., BGP/MPLS IP VPN [RFC4364]) from a service definition
+ perspective. That is, an L3 NVE provides per-tenant forwarding and
+
+
+
+Lasserre, et al. Informational [Page 11]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+ routing instance (L3 VNI) and L3 (IP/MPLS) tunneling encapsulation of
+ tenant IP packets across the underlay. Note that routing could be
+ performed locally on the NVE or in a separate control entity.
+
+2.4. Operational Management Considerations
+
+ NVO3 services are overlay services over an IP underlay.
+
+ As far as the IP underlay is concerned, existing IP Operations,
+ Administration, and Maintenance (OAM) facilities are used.
+
+ With regard to the NVO3 overlay, both L2 and L3 services can be
+ offered. It is expected that existing fault and performance OAM
+ facilities will be used. Sections 4.1 and 4.2.6 provide further
+ discussion of additional fault and performance management issues to
+ consider.
+
+ As far as configuration is concerned, the DC environment is driven by
+ the need to bring new services up rapidly and is typically very
+ dynamic, specifically in the context of virtualized services. It is
+ therefore critical to automate the configuration of NVO3 services.
+
+3. Functional Components
+
+ This section decomposes the network virtualization architecture into
+ the functional components described in Figure 3 to make it easier to
+ discuss solution options for these components.
+
+3.1. Service Virtualization Components
+
+3.1.1. Virtual Access Points (VAPs)
+
+ Tenant Systems are connected to VNIs through Virtual Access Points
+ (VAPs).
+
+ VAPs can be physical ports or virtual ports identified through
+ logical interface identifiers (e.g., VLAN ID and internal vSwitch
+ Interface ID connected to a VM).
+
+3.1.2. Virtual Network Instance (VNI)
+
+ A VNI is a specific VN instance on an NVE. Each VNI defines a
+ forwarding context that contains reachability information and
+ policies.
+
+
+
+
+
+
+
+Lasserre, et al. Informational [Page 12]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+3.1.3. Overlay Modules and VN Context
+
+ Mechanisms for identifying each tenant service are required to allow
+ the simultaneous overlay of multiple tenant services over the same
+ underlay L3 network topology. In the data plane, each NVE, upon
+ sending a tenant packet, must be able to encode the VN Context for
+ the destination NVE in addition to the L3 tunneling information
+ (e.g., source IP address identifying the source NVE and the
+ destination IP address identifying the destination NVE, or MPLS
+ label). This allows the destination NVE to identify the tenant
+ service instance and therefore appropriately process and forward the
+ tenant packet.
+
+ The overlay module provides tunneling overlay functions: tunnel
+ initiation/termination as in the case of stateful tunnels (see
+ Section 3.1.4) and/or encapsulation/decapsulation of frames from the
+ VAPs/L3 underlay.
+
+ In a multi-tenant context, tunneling aggregates frames from/to
+ different VNIs. Tenant identification and traffic demultiplexing are
+ based on the VN Context identifier.
+
+ The following approaches can be considered:
+
+ - VN Context identifier per Tenant: This is a globally unique (on a
+ per-DC administrative domain) VN identifier used to identify the
+ corresponding VNI. Examples of such identifiers in existing
+ technologies are IEEE VLAN IDs and Service Instance IDs (I-SIDs)
+ that identify virtual L2 domains when using IEEE 802.1Q and IEEE
+ 802.1ah, respectively. Note that multiple VN identifiers can
+ belong to a tenant.
+
+ - One VN Context identifier per VNI: Each VNI value is automatically
+ generated by the egress NVE, or a control plane associated with
+ that NVE, and usually distributed by a control-plane protocol to
+ all the related NVEs. An example of this approach is the use of
+ per-VRF MPLS labels in IP VPN [RFC4364]. The VNI value is
+ therefore locally significant to the egress NVE.
+
+ - One VN Context identifier per VAP: A value locally significant to
+ an NVE is assigned and usually distributed by a control-plane
+ protocol to identify a VAP. An example of this approach is the
+ use of per-CE MPLS labels in IP VPN [RFC4364].
+
+ Note that when using one VN Context per VNI or per VAP, an additional
+ global identifier (e.g., a VN identifier or name) may be used by the
+ control plane to identify the tenant context.
+
+
+
+
+Lasserre, et al. Informational [Page 13]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+3.1.4. Tunnel Overlays and Encapsulation Options
+
+ Once the VN Context identifier is added to the frame, an L3 tunnel
+ encapsulation is used to transport the frame to the destination NVE.
+
+ Different IP tunneling options (e.g., Generic Routing Encapsulation
+ (GRE), the Layer 2 Tunneling Protocol (L2TP), and IPsec) and MPLS
+ tunneling can be used. Tunneling could be stateless or stateful.
+ Stateless tunneling simply entails the encapsulation of a tenant
+ packet with another header necessary for forwarding the packet across
+ the underlay (e.g., IP tunneling over an IP underlay). Stateful
+ tunneling, on the other hand, entails maintaining tunneling state at
+ the tunnel endpoints (i.e., NVEs). Tenant packets on an ingress NVE
+ can then be transmitted over such tunnels to a destination (egress)
+ NVE by encapsulating the packets with a corresponding tunneling
+ header. The tunneling state at the endpoints may be configured or
+ dynamically established. Solutions should specify the tunneling
+ technology used and whether it is stateful or stateless. In this
+ document, however, tunneling and tunneling encapsulation are used
+ interchangeably to simply mean the encapsulation of a tenant packet
+ with a tunneling header necessary to carry the packet between an
+ ingress NVE and an egress NVE across the underlay. It should be
+ noted that stateful tunneling, especially when configuration is
+ involved, does impose management overhead and scale constraints.
+ When confidentiality is required, the use of opportunistic security
+ [OPPSEC] can be used as a stateless tunneling solution.
+
+3.1.5. Control-Plane Components
+
+3.1.5.1. Distributed vs. Centralized Control Plane
+
+ Control- and management-plane entities can be centralized or
+ distributed. Both approaches have been used extensively in the past.
+ The routing model of the Internet is a good example of a distributed
+ approach. Transport networks have usually used a centralized
+ approach to manage transport paths.
+
+ It is also possible to combine the two approaches, i.e., using a
+ hybrid model. A global view of network state can have many benefits,
+ but it does not preclude the use of distributed protocols within the
+ network. Centralized models provide a facility to maintain global
+ state and distribute that state to the network. When used in
+ combination with distributed protocols, greater network efficiencies,
+ improved reliability, and robustness can be achieved. Domain- and/or
+ deployment-specific constraints define the balance between
+ centralized and distributed approaches.
+
+
+
+
+
+Lasserre, et al. Informational [Page 14]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+3.1.5.2. Auto-provisioning and Service Discovery
+
+ NVEs must be able to identify the appropriate VNI for each Tenant
+ System. This is based on state information that is often provided by
+ external entities. For example, in an environment where a VM is a
+ Tenant System, this information is provided by VM orchestration
+ systems, since these are the only entities that have visibility of
+ which VM belongs to which tenant.
+
+ A mechanism for communicating this information to the NVE is
+ required. VAPs have to be created and mapped to the appropriate VNI.
+ Depending upon the implementation, this control interface can be
+ implemented using an auto-discovery protocol between Tenant Systems
+ and their local NVE or through management entities. In either case,
+ appropriate security and authentication mechanisms to verify that
+ Tenant System information is not spoofed or altered are required.
+ This is one critical aspect for providing integrity and tenant
+ isolation in the system.
+
+ NVEs may learn reachability information for VNIs on other NVEs via a
+ control protocol that exchanges such information among NVEs or via a
+ management-control entity.
+
+3.1.5.3. Address Advertisement and Tunnel Mapping
+
+ As traffic reaches an ingress NVE on a VAP, a lookup is performed to
+ determine which NVE or local VAP the packet needs to be sent to. If
+ the packet is to be sent to another NVE, the packet is encapsulated
+ with a tunnel header containing the destination information
+ (destination IP address or MPLS label) of the egress NVE.
+ Intermediate nodes (between the ingress and egress NVEs) switch or
+ route traffic based upon the tunnel destination information.
+
+ A key step in the above process consists of identifying the
+ destination NVE the packet is to be tunneled to. NVEs are
+ responsible for maintaining a set of forwarding or mapping tables
+ that hold the bindings between destination VM and egress NVE
+ addresses. Several ways of populating these tables are possible:
+ control plane driven, management plane driven, or data plane driven.
+
+ When a control-plane protocol is used to distribute address
+ reachability and tunneling information, the auto-provisioning and
+ service discovery could be accomplished by the same protocol. In
+ this scenario, the auto-provisioning and service discovery could be
+ combined with (be inferred from) the address advertisement and
+ associated tunnel mapping. Furthermore, a control-plane protocol
+
+
+
+
+
+Lasserre, et al. Informational [Page 15]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+ that carries both MAC and IP addresses eliminates the need for the
+ Address Resolution Protocol (ARP) and hence addresses one of the
+ issues with explosive ARP handling as discussed in [RFC6820].
+
+3.1.5.4. Overlay Tunneling
+
+ For overlay tunneling, and dependent upon the tunneling technology
+ used for encapsulating the Tenant System packets, it may be
+ sufficient to have one or more local NVE addresses assigned and used
+ in the source and destination fields of a tunneling encapsulation
+ header. Other information that is part of the tunneling
+ encapsulation header may also need to be configured. In certain
+ cases, local NVE configuration may be sufficient while in other
+ cases, some tunneling-related information may need to be shared among
+ NVEs. The information that needs to be shared will be technology
+ dependent. For instance, potential information could include tunnel
+ identity, encapsulation type, and/or tunnel resources. In certain
+ cases, such as when using IP multicast in the underlay, tunnels that
+ interconnect NVEs may need to be established. When tunneling
+ information needs to be exchanged or shared among NVEs, a control-
+ plane protocol may be required. For instance, it may be necessary to
+ provide active/standby status information between NVEs, up/down
+ status information, pruning/grafting information for multicast
+ tunnels, etc.
+
+ In addition, a control plane may be required to set up the tunnel
+ path for some tunneling technologies. This applies to both unicast
+ and multicast tunneling.
+
+3.2. Multihoming
+
+ Multihoming techniques can be used to increase the reliability of an
+ NVO3 network. It is also important to ensure that the physical
+ diversity in an NVO3 network is taken into account to avoid single
+ points of failure.
+
+ Multihoming can be enabled in various nodes, from Tenant Systems into
+ ToRs, ToRs into core switches/routers, and core nodes into DC GWs.
+
+ The NVO3 underlay nodes (i.e., from NVEs to DC GWs) rely on IP
+ routing techniques or MPLS re-rerouting capabilities as the means to
+ re-route traffic upon failures.
+
+ When a Tenant System is co-located with the NVE, the Tenant System is
+ effectively single-homed to the NVE via a virtual port. When the
+ Tenant System and the NVE are separated, the Tenant System is
+ connected to the NVE via a logical L2 construct such as a VLAN, and
+ it can be multihomed to various NVEs. An NVE may provide an L2
+
+
+
+Lasserre, et al. Informational [Page 16]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+ service to the end system or an l3 service. An NVE may be multihomed
+ to a next layer in the DC at L2 or L3. When an NVE provides an L2
+ service and is not co-located with the end system, loop-avoidance
+ techniques must be used. Similarly, when the NVE provides L3
+ service, similar dual-homing techniques can be used. When the NVE
+ provides an L3 service to the end system, it is possible that no
+ dynamic routing protocol is enabled between the end system and the
+ NVE. The end system can be multihomed to multiple physically
+ separated L3 NVEs over multiple interfaces. When one of the links
+ connected to an NVE fails, the other interfaces can be used to reach
+ the end system.
+
+ External connectivity from a DC can be handled by two or more DC
+ gateways. Each gateway provides access to external networks such as
+ VPNs or the Internet. A gateway may be connected to two or more edge
+ nodes in the external network for redundancy. When a connection to
+ an upstream node is lost, the alternative connection is used, and the
+ failed route withdrawn.
+
+3.3. VM Mobility
+
+ In DC environments utilizing VM technologies, an important feature is
+ that VMs can move from one server to another server in the same or
+ different L2 physical domains (within or across DCs) in a seamless
+ manner.
+
+ A VM can be moved from one server to another in stopped or suspended
+ state ("cold" VM mobility) or in running/active state ("hot" VM
+ mobility). With "hot" mobility, VM L2 and L3 addresses need to be
+ preserved. With "cold" mobility, it may be desired to preserve at
+ least VM L3 addresses.
+
+ Solutions to maintain connectivity while a VM is moved are necessary
+ in the case of "hot" mobility. This implies that connectivity among
+ VMs is preserved. For instance, for L2 VNs, ARP caches are updated
+ accordingly.
+
+ Upon VM mobility, NVE policies that define connectivity among VMs
+ must be maintained.
+
+ During VM mobility, it is expected that the path to the VM's default
+ gateway assures adequate QoS to VM applications, i.e., QoS that
+ matches the expected service-level agreement for these applications.
+
+4. Key Aspects of Overlay Networks
+
+ The intent of this section is to highlight specific issues that
+ proposed overlay solutions need to address.
+
+
+
+Lasserre, et al. Informational [Page 17]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+4.1. Pros and Cons
+
+ An overlay network is a layer of virtual network topology on top of
+ the physical network.
+
+ Overlay networks offer the following key advantages:
+
+ - Unicast tunneling state management and association of Tenant
+ Systems reachability are handled at the edge of the network (at
+ the NVE). Intermediate transport nodes are unaware of such state.
+ Note that when multicast is enabled in the underlay network to
+ build multicast trees for tenant VNs, there would be more state
+ related to tenants in the underlay core network.
+
+ - Tunneling is used to aggregate traffic and hide tenant addresses
+ from the underlay network and hence offers the advantage of
+ minimizing the amount of forwarding state required within the
+ underlay network.
+
+ - Decoupling of the overlay addresses (MAC and IP) used by VMs from
+ the underlay network provides tenant separation and separation of
+ the tenant address spaces from the underlay address space.
+
+
+ - Overlay networks support of a large number of virtual network
+ identifiers.
+
+ Overlay networks also create several challenges:
+
+ - Overlay networks typically have no control of underlay networks
+ and lack underlay network information (e.g., underlay
+ utilization):
+
+ o Overlay networks and/or their associated management entities
+ typically probe the network to measure link or path properties,
+ such as available bandwidth or packet loss rate. It is
+ difficult to accurately evaluate network properties. It might
+ be preferable for the underlay network to expose usage and
+ performance information.
+
+ o Miscommunication or lack of coordination between overlay and
+ underlay networks can lead to an inefficient usage of network
+ resources.
+
+ o When multiple overlays co-exist on top of a common underlay
+ network, the lack of coordination between overlays can lead to
+ performance issues and/or resource usage inefficiencies.
+
+
+
+
+Lasserre, et al. Informational [Page 18]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+ - Traffic carried over an overlay might fail to traverse firewalls
+ and NAT devices.
+
+ - Multicast service scalability: Multicast support may be required
+ in the underlay network to address tenant flood containment or
+ efficient multicast handling. The underlay may also be required
+ to maintain multicast state on a per-tenant basis or even on a
+ per-individual multicast flow of a given tenant. Ingress
+ replication at the NVE eliminates that additional multicast state
+ in the underlay core, but depending on the multicast traffic
+ volume, it may cause inefficient use of bandwidth.
+
+4.2. Overlay Issues to Consider
+
+4.2.1. Data Plane vs. Control Plane Driven
+
+ In the case of an L2 NVE, it is possible to dynamically learn MAC
+ addresses against VAPs. It is also possible that such addresses be
+ known and controlled via management or a control protocol for both L2
+ NVEs and L3 NVEs. Dynamic data-plane learning implies that flooding
+ of unknown destinations be supported and hence implies that broadcast
+ and/or multicast be supported or that ingress replication be used as
+ described in Section 4.2.3. Multicasting in the underlay network for
+ dynamic learning may lead to significant scalability limitations.
+ Specific forwarding rules must be enforced to prevent loops from
+ happening. This can be achieved using a spanning tree, a shortest
+ path tree, or a split-horizon mesh.
+
+ It should be noted that the amount of state to be distributed is
+ dependent upon network topology and the number of virtual machines.
+ Different forms of caching can also be utilized to minimize state
+ distribution between the various elements. The control plane should
+ not require an NVE to maintain the locations of all the Tenant
+ Systems whose VNs are not present on the NVE. The use of a control
+ plane does not imply that the data plane on NVEs has to maintain all
+ the forwarding state in the control plane.
+
+4.2.2. Coordination between Data Plane and Control Plane
+
+ For an L2 NVE, the NVE needs to be able to determine MAC addresses of
+ the Tenant Systems connected via a VAP. This can be achieved via
+ data-plane learning or a control plane. For an L3 NVE, the NVE needs
+ to be able to determine the IP addresses of the Tenant Systems
+ connected via a VAP.
+
+
+
+
+
+
+
+Lasserre, et al. Informational [Page 19]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+ In both cases, coordination with the NVE control protocol is needed
+ such that when the NVE determines that the set of addresses behind a
+ VAP has changed, it triggers the NVE control plane to distribute this
+ information to its peers.
+
+4.2.3. Handling Broadcast, Unknown Unicast, and Multicast (BUM) Traffic
+
+ There are several options to support packet replication needed for
+ broadcast, unknown unicast, and multicast. Typical methods include:
+
+ - Ingress replication
+
+ - Use of underlay multicast trees
+
+ There is a bandwidth vs. state trade-off between the two approaches.
+ Depending upon the degree of replication required (i.e., the number
+ of hosts per group) and the amount of multicast state to maintain,
+ trading bandwidth for state should be considered.
+
+ When the number of hosts per group is large, the use of underlay
+ multicast trees may be more appropriate. When the number of hosts is
+ small (e.g., 2-3) and/or the amount of multicast traffic is small,
+ ingress replication may not be an issue.
+
+ Depending upon the size of the data center network and hence the
+ number of (S,G) entries, and also the duration of multicast flows,
+ the use of underlay multicast trees can be a challenge.
+
+ When flows are well known, it is possible to pre-provision such
+ multicast trees. However, it is often difficult to predict
+ application flows ahead of time; hence, programming of (S,G) entries
+ for short-lived flows could be impractical.
+
+ A possible trade-off is to use in the underlay shared multicast trees
+ as opposed to dedicated multicast trees.
+
+4.2.4. Path MTU
+
+ When using overlay tunneling, an outer header is added to the
+ original frame. This can cause the MTU of the path to the egress
+ tunnel endpoint to be exceeded.
+
+ It is usually not desirable to rely on IP fragmentation for
+ performance reasons. Ideally, the interface MTU as seen by a Tenant
+ System is adjusted such that no fragmentation is needed.
+
+
+
+
+
+
+Lasserre, et al. Informational [Page 20]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+ It is possible for the MTU to be configured manually or to be
+ discovered dynamically. Various Path MTU discovery techniques exist
+ in order to determine the proper MTU size to use:
+
+ - Classical ICMP-based Path MTU Discovery [RFC1191] [RFC1981]
+
+ Tenant Systems rely on ICMP messages to discover the MTU of the
+ end-to-end path to its destination. This method is not always
+ possible, such as when traversing middleboxes (e.g., firewalls)
+ that disable ICMP for security reasons.
+
+ - Extended Path MTU Discovery techniques such as those defined in
+ [RFC4821]
+
+ Tenant Systems send probe packets of different sizes and rely on
+ confirmation of receipt or lack thereof from receivers to allow a
+ sender to discover the MTU of the end-to-end paths.
+
+ While it could also be possible to rely on the NVE to perform
+ segmentation and reassembly operations without relying on the Tenant
+ Systems to know about the end-to-end MTU, this would lead to
+ undesired performance and congestion issues as well as significantly
+ increase the complexity of hardware NVEs required for buffering and
+ reassembly logic.
+
+ Preferably, the underlay network should be designed in such a way
+ that the MTU can accommodate the extra tunneling and possibly
+ additional NVO3 header encapsulation overhead.
+
+4.2.5. NVE Location Trade-Offs
+
+ In the case of DC traffic, traffic originated from a VM is native
+ Ethernet traffic. This traffic can be switched by a local virtual
+ switch or ToR switch and then by a DC gateway. The NVE function can
+ be embedded within any of these elements.
+
+ There are several criteria to consider when deciding where the NVE
+ function should happen:
+
+ - Processing and memory requirements
+
+ o Datapath (e.g., lookups, filtering, and
+ encapsulation/decapsulation)
+
+ o Control-plane processing (e.g., routing, signaling, and OAM)
+ and where specific control-plane functions should be enabled
+
+ - FIB/RIB size
+
+
+
+Lasserre, et al. Informational [Page 21]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+ - Multicast support
+
+ o Routing/signaling protocols
+
+ o Packet replication capability
+
+ o Multicast FIB
+
+ - Fragmentation support
+
+ - QoS support (e.g., marking, policing, and queuing)
+
+ - Resiliency
+
+4.2.6. Interaction between Network Overlays and Underlays
+
+ When multiple overlays co-exist on top of a common underlay network,
+ resources (e.g., bandwidth) should be provisioned to ensure that
+ traffic from overlays can be accommodated and QoS objectives can be
+ met. Overlays can have partially overlapping paths (nodes and
+ links).
+
+ Each overlay is selfish by nature. It sends traffic so as to
+ optimize its own performance without considering the impact on other
+ overlays, unless the underlay paths are traffic engineered on a per-
+ overlay basis to avoid congestion of underlay resources.
+
+ Better visibility between overlays and underlays, or general
+ coordination in placing overlay demands on an underlay network, may
+ be achieved by providing mechanisms to exchange performance and
+ liveliness information between the underlay and overlay(s) or by the
+ use of such information by a coordination system. Such information
+ may include:
+
+ - Performance metrics (throughput, delay, loss, jitter) such as
+ defined in [RFC3148], [RFC2679], [RFC2680], and [RFC3393].
+
+ - Cost metrics
+
+5. Security Considerations
+
+ There are three points of view when considering security for NVO3.
+ First, the service offered by a service provider via NVO3 technology
+ to a tenant must meet the mutually agreed security requirements.
+ Second, a network implementing NVO3 must be able to trust the virtual
+ network identity associated with packets received from a tenant.
+ Third, an NVO3 network must consider the security associated with
+ running as an overlay across the underlay network.
+
+
+
+Lasserre, et al. Informational [Page 22]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+ To meet a tenant's security requirements, the NVO3 service must
+ deliver packets from the tenant to the indicated destination(s) in
+ the overlay network and external networks. The NVO3 service provides
+ data confidentiality through data separation. The use of both VNIs
+ and tunneling of tenant traffic by NVEs ensures that NVO3 data is
+ kept in a separate context and thus separated from other tenant
+ traffic. The infrastructure supporting an NVO3 service (e.g.,
+ management systems, NVEs, NVAs, and intermediate underlay networks)
+ should be limited to authorized access so that data integrity can be
+ expected. If a tenant requires that its data be confidential, then
+ the Tenant System may choose to encrypt its data before transmission
+ into the NVO3 service.
+
+ An NVO3 service must be able to verify the VNI received on a packet
+ from the tenant. To ensure this, not only tenant data but also NVO3
+ control data must be secured (e.g., control traffic between NVAs and
+ NVEs, between NVAs, and between NVEs). Since NVEs and NVAs play a
+ central role in NVO3, it is critical that secure access to NVEs and
+ NVAs be ensured such that no unauthorized access is possible. As
+ discussed in Section 3.1.5.2, identification of Tenant Systems is
+ based upon state that is often provided by management systems (e.g.,
+ a VM orchestration system in a virtualized environment). Secure
+ access to such management systems must also be ensured. When an NVE
+ receives data from a Tenant System, the tenant identity needs to be
+ verified in order to guarantee that it is authorized to access the
+ corresponding VN. This can be achieved by identifying incoming
+ packets against specific VAPs in some cases. In other circumstances,
+ authentication may be necessary. Once this verification is done, the
+ packet is allowed into the NVO3 overlay, and no integrity protection
+ is provided on the overlay packet encapsulation (e.g., the VNI,
+ destination NVE, etc.).
+
+ Since an NVO3 service can run across diverse underlay networks, when
+ the underlay network is not trusted to provide at least data
+ integrity, data encryption is needed to assure correct packet
+ delivery.
+
+ It is also desirable to restrict the types of information (e.g.,
+ topology information as discussed in Section 4.2.6) that can be
+ exchanged between an NVO3 service and underlay networks based upon
+ their agreed security requirements.
+
+
+
+
+
+
+
+
+
+
+Lasserre, et al. Informational [Page 23]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+6. Informative References
+
+ [EVPN] Sajassi, A., Aggarwal, R., Bitar, N., Isaac, A., and J.
+ Uttaro, "BGP MPLS Based Ethernet VPN", Work in Progress,
+ draft-ietf-l2vpn-evpn-10, October 2014.
+
+ [OPPSEC] Dukhovni, V. "Opportunistic Security: Some Protection Most
+ of the Time", Work in Progress, draft-dukhovni-
+ opportunistic-security-04, August 2014.
+
+ [RFC1191] Mogul, J. and S. Deering, "Path MTU discovery", RFC 1191,
+ November 1990, <http://www.rfc-editor.org/info/rfc1191>.
+
+ [RFC1981] McCann, J., Deering, S., and J. Mogul, "Path MTU Discovery
+ for IP version 6", RFC 1981, August 1996,
+ <http://www.rfc-editor.org/info/rfc1981>.
+
+ [RFC2679] Almes, G., Kalidindi, S., and M. Zekauskas, "A One-way
+ Delay Metric for IPPM", RFC 2679, September 1999,
+ <http://www.rfc-editor.org/info/rfc2679>.
+
+ [RFC2680] Almes, G., Kalidindi, S., and M. Zekauskas, "A One-way
+ Packet Loss Metric for IPPM", RFC 2680, September 1999,
+ <http://www.rfc-editor.org/info/rfc2680>.
+
+ [RFC3148] Mathis, M. and M. Allman, "A Framework for Defining
+ Empirical Bulk Transfer Capacity Metrics", RFC 3148, July
+ 2001, <http://www.rfc-editor.org/info/rfc3148>.
+
+ [RFC3393] Demichelis, C. and P. Chimento, "IP Packet Delay Variation
+ Metric for IP Performance Metrics (IPPM)", RFC 3393,
+ November 2002, <http://www.rfc-editor.org/info/rfc3393>.
+
+ [RFC4364] Rosen, E. and Y. Rekhter, "BGP/MPLS IP Virtual Private
+ Networks (VPNs)", RFC 4364, February 2006,
+ <http://www.rfc-editor.org/info/rfc4364>.
+
+ [RFC4761] Kompella, K., Ed., and Y. Rekhter, Ed., "Virtual Private
+ LAN Service (VPLS) Using BGP for Auto-Discovery and
+ Signaling", RFC 4761, January 2007,
+ <http://www.rfc-editor.org/info/rfc4761>.
+
+ [RFC4762] Lasserre, M., Ed., and V. Kompella, Ed., "Virtual Private
+ LAN Service (VPLS) Using Label Distribution Protocol (LDP)
+ Signaling", RFC 4762, January 2007,
+ <http://www.rfc-editor.org/info/rfc4762>.
+
+
+
+
+
+Lasserre, et al. Informational [Page 24]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+ [RFC4821] Mathis, M. and J. Heffner, "Packetization Layer Path MTU
+ Discovery", RFC 4821, March 2007,
+ <http://www.rfc-editor.org/info/rfc4821>.
+
+ [RFC6820] Narten, T., Karir, M., and I. Foo, "Address Resolution
+ Problems in Large Data Center Networks", RFC 6820, January
+ 2013, <http://www.rfc-editor.org/info/rfc6820>.
+
+ [RFC7364] Narten, T., Ed., Gray, E., Ed., Black, D., Fang, L.,
+ Kreeger, L., and M. Napierala, "Problem Statement:
+ Overlays for Network Virtualization", RFC 7364, October
+ 2014, <http://www.rfc-editor.org/info/rfc7364>.
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+Lasserre, et al. Informational [Page 25]
+
+RFC 7365 Framework for DC Network Virtualization October 2014
+
+
+Acknowledgments
+
+ In addition to the authors, the following people contributed to this
+ document: Dimitrios Stiliadis, Rotem Salomonovitch, Lucy Yong, Thomas
+ Narten, Larry Kreeger, and David Black.
+
+Authors' Addresses
+
+ Marc Lasserre
+ Alcatel-Lucent
+ EMail: marc.lasserre@alcatel-lucent.com
+
+
+ Florin Balus
+ Alcatel-Lucent
+ 777 E. Middlefield Road
+ Mountain View, CA 94043
+ United States
+ EMail: florin.balus@alcatel-lucent.com
+
+
+ Thomas Morin
+ Orange
+ EMail: thomas.morin@orange.com
+
+
+ Nabil Bitar
+ Verizon
+ 50 Sylvan Road
+ Waltham, MA 02145
+ United States
+ EMail: nabil.n.bitar@verizon.com
+
+
+ Yakov Rekhter
+ Juniper
+ EMail: yakov@juniper.net
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+Lasserre, et al. Informational [Page 26]
+